Flexible shielded instrumentation and control cable for fixed installations in industrial processes or buildings when certain electromagnetic protection is required as well as good cable performance in case of fire.

*CPR: Cable suitable for installation under the requirements of the CPR regulations (Construction Product Regulation (EU) N°305/2011) in accordance with the

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Shielded cable Cerviflam Z1C4Z1-K (AS) 300/500V CPR
~\ImgCli\FOTO2_381.jpg
Flexible shielded instrumentation and control cable for fixed installations in industrial processes or buildings when certain electromagnetic protection is required as well as good cable performance in case of fire.

*CPR: Cable suitable for installation under the requirements of the CPR regulations (Construction Product Regulation (EU) N°305/2011) in accordance with the classification (Euroclass) specified in this document.
Protegido electromagneticas
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Flexible
Baka corrosividad gases
Construction
1. Conductor
Flexible bare copper wires
Class V Acc. to UNE-EN 60228
2. Insulation
Halogen free compound
Identification: HD 308 S2 (See attached table)
3. Composition
Insulated conductors laid-up together
4. Screen
Bare copper wire braid
Coverage: 60% aprox.
5. Outer sheath
Halogen free compound
Colour: Green
Technical characteristics
1. Operating voltage
300/500 V
2. Test Voltage
2000V
3. Operating Tª (conductor)
Fixed installation: -15°C to +70°C
During installation: 0°C Min.
Short-circuit (Max. 5 seg): 160°C
4. Min. bending radius
8xD
Standards / Properties
1. Ref. for construction/drawing
Special design, based on EN 50288-7
2. CPR Classification (Euroclass)
Cca-s1b,d1,a1
(According to UNE-EN 50575)
3. Flame Retardant
UNE-EN 60332-1 (IEC 60332-1)
4. Fire Retardant
UNE-EN 60332-3 (IEC 60332-3)
5. Halogen free
UNE-EN 60754-1 (IEC 60754-1)
6. Low corrosivity
UNE-EN 60754-2 (IEC 60754-2)
(pH >= 4,3 ; conductivity =< 10µS/mm)
7. Low smoke emission
UNE-EN 61034 (IEC 61034)